                                |  DTSD566-L1107DSSD566-L1107
 |  
                                |  |  
                                |  |  
                                | ¡¡ |  
                                |   |  
                                |  |  
                                |  |  | 
                                
                                
                                | 
                                
                                
                                |  | Three phase multi-functional    
                                  watt-hour meter |  
                                | ¡¡ | ¡¡ |  |  
                                | DTSD566     
                                  / DSSD566 three phase Electronic Multifunction     
                                  Programmable watt-hour meter is a hi-tech     
                                  intelligent energy-measuring instrument     
                                  composed of analog-to-digital converter A/D,     
                                  calendar clock, special microprocessor CPU,     
                                  liquid crystal display LCD and switching power     
                                  supply and so on. This meter can measure     
                                  import/export active/reactive energy, maximum     
                                  demand, power, voltage, current, and perform     
                                  data processing with reference to relative     
                                  tariff.
 It conforms to     
                                  all technical requirements to multi-function     
                                  meter specified in IEC61036, IEC61268,     
                                  IEC60687, IEC61107.
 
 |  
                                | ¡¡ |  
                                | Technical parameters |  
                                | class:               
                                  active:0.5S or 1.0   reactive: 2.0
 rated         
                                  voltage:   DTSD566: 220/380V, 230/400V,       
                                  240/415V  DSSD566:100V
 rated         
                                  current:   1.5(6)A, 5(30)A, 10(40)A,         
                                  15(60)A, 20(80)A, 10(100)A
 power         
                                  loss:      0.5W
 operating temperature:     
                                  -10¡æ-+55¡æ
 
 |  
                                | Main features |  
                                | ¡ö Energy 
                                  measuring function: Measuring import and 
                                  export active energy in each time interval, 
                                  measuring lagging and leading reactive energy, 
                                  four quadrant reactive energy in each time 
                                  interval, Output ports of photoelectric 
                                  coupling for active, reactive, and clock 
                                  impulse independently; ¡ö Multi  
                                  rate function: 4 different tariffs, 2 time  
                                  zones in a year, 10 time periods in a day, the  
                                  meter automatically calculate leap years and  
                                  leap months, display real-time clock; communication 
                                  protocol conforms IEC61107.
 ¡ö Maximum     
                                  demand measuring: Measuring import and export     
                                  maximum demand in each time interval and     
                                  occurrence time, store two months maximum     
                                  demand data, the integration period can be one     
                                  of 15 ,30, 60 minutes and the sliding time can     
                                  be selected between 1,3,5 minute;
 ¡ö 
                                  Recording lost voltage function: The meter     
                                  record the following data into relevant     
                                  voltage loss record of each phase, the date     
                                  and time that voltage loss happens and ends,     
                                  times and accumulative time of voltage loss,     
                                  last ten times record;
 ¡ö 
                                  Recording lost current function: The meter 
                                  record the following data into relevant 
                                  current loss record of each phase, the date 
                                  and time that current loss happens and ends, 
                                  times and accumulative time of current loss, 
                                  last ten times record;
 ¡ö Data 
                                  display: Scroll display parameters and 
                                  measured data by LCD, items and orders in 
                                  scroll display to be customized; the data by 
                                  button display can be customized also;
 ¡ö 
                                  Recording the times of blackout and power on, 
                                  the date of last blackout and power on.
 ¡ö Only 
                                  the authorized person can programs the meter 
                                  by opening the sealed meter cover to access 
                                  program button;
 ¡ö Other 
                                  function:
 The working time of battery; total and each phase     
                                  energy: instant power, voltage, current and     
                                  PF;
 LCD display relative signal when     
                                  phase order is not correct;
 Recording the event of opening     
                                  cover and terminal block cover;
 ¡ö Extend 
                                  function:
 The meter adopts multi-phase power supplying     
                                  circuit to guarantee its normal operation at     
                                  phase missing;
 The data stored in non-volatile     
                                  memory in the event of power failure shall not     
                                  be lost for at least 10 years.
 Twelve month import active energy     
                                  can be provided; Double RS485 communication     
                                  interface, provided infrared interface
 The meter can be awaked to     
                                  realize meter reading; provided backlight LCD
 
 |  
                                | Mounting Dimension |  |