Product Search: Name or model number
¡¡

 DTSD566-L1107
 DSSD566-L1107

¡¡

 

Three phase multi-functional watt-hour meter 
¡¡ ¡¡
    
      DTSD566 / DSSD566 three phase Electronic Multifunction Programmable watt-hour meter is a hi-tech intelligent energy-measuring instrument composed of analog-to-digital converter A/D, calendar clock, special microprocessor CPU, liquid crystal display LCD and switching power supply and so on. This meter can measure import/export active/reactive energy, maximum demand, power, voltage, current, and perform data processing with reference to relative tariff. 
      It conforms to all technical requirements to multi-function meter specified in IEC61036, IEC61268, IEC60687, IEC61107.

¡¡
Technical parameters
     
     class:           active:0.5S or 1.0   reactive: 2.0 
     rated voltage:   DTSD566: 220/380V, 230/400V, 240/415V  DSSD566:100V
     rated current:   1.5(6)A, 5(30)A, 10(40)A, 15(60)A, 20(80)A, 10(100)A
     power loss:      0.5W
     operating temperature: -10¡æ-+55¡æ
     
Main features
 ¡ö Energy measuring function: Measuring import and export active energy in each time interval, measuring lagging and leading reactive energy, four quadrant reactive energy in each time interval, Output ports of photoelectric coupling for active, reactive, and clock impulse independently;
 ¡ö Multi rate function: 4 different tariffs, 2 time zones in a year, 10 time periods in a day, the meter automatically calculate leap years and leap months, display real-time clock; communication protocol conforms IEC61107.
 ¡ö Maximum demand measuring: Measuring import and export maximum demand in each time interval and occurrence time, store two months maximum demand data, the integration period can be one of 15 ,30, 60 minutes and the sliding time can be selected between 1,3,5 minute; 
 ¡ö Recording lost voltage function: The meter record the following data into relevant voltage loss record of each phase, the date and time that voltage loss happens and ends, times and accumulative time of voltage loss, last ten times record; 
 ¡ö Recording lost current function: The meter record the following data into relevant current loss record of each phase, the date and time that current loss happens and ends, times and accumulative time of current loss, last ten times record;
 ¡ö Data display: Scroll display parameters and measured data by LCD, items and orders in scroll display to be customized; the data by button display can be customized also;
 ¡ö Recording the times of blackout and power on, the date of last blackout and power on.
 ¡ö Only the authorized person can programs the meter by opening the sealed meter cover to access program button;
 ¡ö Other function:
   The working time of battery; total and each phase energy: instant power, voltage, current and PF;
   LCD display relative signal when phase order is not correct;
   Recording the event of opening cover and terminal block cover;
 ¡ö Extend function:
   The meter adopts multi-phase power supplying circuit to guarantee its normal operation at phase missing;
   The data stored in non-volatile memory in the event of power failure shall not be lost for at least 10 years.
   Twelve month import active energy can be provided; Double RS485 communication interface, provided infrared interface
   The meter can be awaked to realize meter reading; provided backlight LCD
  
Mounting Dimension
¡¡
 

                                                                                                                

¡¡